Repairing a heated floor in a hammam. Why you shouldn't install a heating cable in the insulation under mosaic tiles.
Any heating cable must be surrounded by a layer of tile adhesive or screed to allow it to transfer all of its generated heat into this layer. If this heat-conducting layer of mortar above the cable is reduced, the heating cable will overheat, causing a short circuit or self-destruction.
In a room with high temperatures, such as a hammam, it is prohibited to use a heating cable placed in the grooves of the insulation and sealed with tile adhesive. Instead, use a thin heating mat with good Teflon insulation or create a sufficient layer of mortar above the heating cable to allow heat dissipation.
If you don't want to remodel a hammam with a heating cable installed in the insulation, be sure to watch this video.
For more information on choosing underfloor heating, installing underfloor heating, and properly connecting underfloor heating, please visit the blog page on electric heating systems: