JustAnswer Customer: How can I correct an Error Code #79 for a Trane Confort Control referred to in TCONT900AC43UA
gotoman for ac: HVAC Technician: That is open low pressure switch.
gotoman for ac: HVAC Technician: Hard lockout.
gotoman for ac: HVAC Technician: Possible causes System low on charge--Cooling indoor air flow restricted(dirty coil or filters)-- Turn off power to inside and outside unit and system will reset.
gotoman for ac: HVAC Technician: Check filters and if they are OK have refrigerant charge checked.
gotoman for ac: HVAC Technician: Russ