As a software developer and IT technician, I’m less interested in the "magic" of radio signals and more focused on bridging the gap between software and hardware. I treat professional, military, and commercial radios as data transport layers—experimenting with SSH over DMR, digital data transmission, and solar-powered IT infrastructure.
I acquire surplus gear and customer returns to document the process of restoring it to service or repurposing it for modern digital communication needs.
Support the projects:
If you find value in this technical documentation and want to help fund the acquisition of unique gear for future experiments, you can leave a tip here: https://ko-fi.com/electronicnoobblog
Every bit goes toward hardware for the lab. Thanks for being part of the community! 🛠️ ELTEK EVD-MIN 1kVa
Error code is: 09
Problem is interesting, when UPS is disconnected from utility I can
successfully do "cold start" and enable inverter output - i tested using
10% nominal load and everything work just like we expect from batteries.
When i connect utility UPS start recharging batteries.
But when I enable UPS output, while having connected utility - it show
error code 09 and bypass output.
User manual does not point that error code.
Cause was shorted bridge rectifier that trigger protective inline fuse T6.3A. Simple fix, great satisfaction - it's a keeper.