Students training aid for testing insulation resistance. Demonstration shows how an insulation resistance test could damage a USB socket outlet and how to overcome this. Test voltage is 500V DC and the minimum acceptable value according to BS 7671 is 1 megohm for the whole installation with further investigation when the reading falls below 2 megohms.
Note a 3 lead low earth fault loop impedance test will pickup if you have forgotten to reconnect either the line(s) or neutral(s) of the UBS socket outlet.