How to Connect up a Contactor Control so 2 way Switching can Control a Large Load

Опубликовано: 18 Апрель 2026
на канале: GSH Electrical
145,423
1.8k

Matt draws out how a contactor can be controlled by 2 way switch and be used to turn on many heavy current drawing loads. We see how many lighting points say in a factory can be turned on by a simple light switch via a contactor.

NOTE: This is a wiring diagram and the cable runs in reality will be completely different. The rated value of the contactor will vary depending on the load current being supplied.

== 🕐 Time Stamps - Cut to the action 🕕 ==

00:00 - Contactor controlled loads
00:30 - Contactor
01:06 - Distribution board
01:56 - 2 way switching
02:48 - Switch to A1 on the contactor
03:25 - Neutral to A2 on the contactor
04:45 - Affect of electricity explained in the coil
05:34 - De-energizing the contactor explained
06:01 - Power to our loads via the contactor
07:30 - Contactor outgoing side to the loads
09:00 - Large loads
10:10 - Circuit is off
10:25 - Circuit is on
11:25 - 54 amps controlled from a 10 amp switch

🔵 The 2 plate method of wiring lighting circuits playlist    • Taking the Feed (Supply) to the Light Swit...  

Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.