Fixing a stuck microswitch in a 2-port zone value, which was causing my boiler to fire erratically!

Опубликовано: 05 Март 2026
на канале: Tomas McGuinness
2,230
33

In this video I investigate the cause of what I initially feared was a gas leak, but what turned out to be a stuck microswitch within a 2-port zone value.

After an emergency visit from Cadent confirmed there was no leak, I set about investigating why my boiler was using gas, despite the thermostat being off.

Follow along as I trace the source of the problem, eventually discovering the fault was the microswitch inside my Under Floor Heating Two Port Zone valve. Thankfully I was able to get the switch working again (some dirt perhaps?) and my issue is resolved!

If you suspect you might have a gas leak, phone Cadent immediately!!! https://cadentgas.com/contact-us

If you'd like to support me - https://ko-fi.com/tomasmcguinness

Check out my blog - https://tomasmcguinness.com

Find me on X - https://www.x.com/tomasmcguinness